How many fire extinguishers does a construction site need, and where do they go?

Quick answer

At least one 2A-rated extinguisher for each 3,000 square feet of protected building area, with no more than 100 feet of travel from any point to the nearest one (29 CFR 1926.150(c)(1)(i)). Multistory buildings need at least one per floor, with one adjacent to the stairway (1926.150(c)(1)(iv)), and a 10B extinguisher must be within 50 feet of anywhere more than 5 gallons of flammable or combustible liquid or 5 pounds of flammable gas is in use (1926.150(c)(1)(vi)).

The construction fire protection standard answers this with three numbers, and most sites get the first one right and forget the other two.

Area and travel distance. A fire extinguisher rated not less than 2A must be provided for each 3,000 square feet of the protected building area, or major fraction thereof, and travel distance from any point of the protected area to the nearest extinguisher may not exceed 100 feet (29 CFR 1926.150(c)(1)(i)). Both conditions apply: a large open floor may satisfy the area count and still have a corner more than 100 feet from the nearest unit.

Floors. One or more extinguishers rated not less than 2A must be provided on each floor, and in multistory buildings at least one must be located adjacent to the stairway (29 CFR 1926.150(c)(1)(iv)).

Flammables. An extinguisher rated not less than 10B must be within 50 feet of wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are being used on the jobsite; integral fuel tanks of motor vehicles do not count (29 CFR 1926.150(c)(1)(vi)). A roofing kettle, a generator fueling station, or a cutting-torch setup each trips this one.

Upkeep. Firefighting equipment must be conspicuously located, periodically inspected, and maintained in operating condition; defective equipment is replaced immediately (29 CFR 1926.150(a)(3), 1926.150(a)(4)). Access to all available firefighting equipment must be maintained at all times (29 CFR 1926.150(a)(2)).

29 CFR 1926.150(c)(1)(i)29 CFR 1926.150(c)(1)(iv)29 CFR 1926.150(c)(1)(vi)29 CFR 1926.150(a)(2)29 CFR 1926.150(a)(3)29 CFR 1926.150(a)(4)
Source: An analysis from the construction fire protection standard, 29 CFR 1926 Subpart F (1926.150). Primary reference: read it on osha.gov →

Federal rule shown. If the workplace is in one of the 29 State Plan states and territories, the state standard governs and may differ — see Known Limitations.

Need the passage itself?

Canary AI has indexed all of federal OSHA — 7,220 passages of 29 CFR and 279 interpretation letters — and finds the exact section for a question, with a link to the official text. Free, no sign-up, nothing collected.

Open the lookup tool →

Related answers

Is HAZWOPER training required for crime scene and blood cleanup crews?General · OSHA letter 2019-09-06Can OSHA posters be stacked with other labor law posters on a wall-mounted hanger?General · OSHA letter 2023-06-15Do stairs at a 49-50 degree angle with an 8-inch run meet OSHA tread depth requirements?General · OSHA letter 2025-06-17