How often do rubber insulating gloves have to be electrically tested under OSHA 1910.137?

Quick answer

Per Table I-5 of 29 CFR 1910.137, rubber insulating gloves must be tested before first issue and every six months thereafter, and also whenever the insulating value is suspect, after repair, and after use without protectors. Gloves that were tested but never issued cannot be placed into service unless they were tested within the previous 12 months.

An Army engineer battalion asked OSHA to clarify glove testing intervals, since the military's Unified Facilities Criteria (UFC 3-560-01) mirrors OSHA's electrical PPE requirements. Their example: gloves tested January 1, 2016 but not issued until October 1, 2016 'must be removed from service by January 1, 2017...two months from the issue date but 12 months from the test date.' They asked whether gloves in service really must be retested on the 12-month clock even if issued only three months earlier, and what 'first issue' means.

OSHA confirmed the intervals in Table I-5 of 29 CFR 1910.137: rubber insulating gloves must be tested before first issue and every six months thereafter, and also upon indication that the insulating value is suspect, after repair, and after use without protectors. Separately, if gloves were electrically tested but not issued for service, they cannot be placed into service unless they were tested within the previous 12 months. OSHA added that best practice involves testing as frequently as monthly during regular use.

On the definition of 'first issue,' OSHA said gloves are first issued when new gloves are 'removed from their original, manufacturer's packaging.' Even if gloves are then tested and returned to storage rather than handed to a worker, they are considered issued for purposes of the use and testing requirements. Safety managers tracking glove inventories should therefore date-track from unpackaging and testing, not just from when a worker actually receives the gloves.

1910.137
Source: OSHA Standard Interpretation letter, 2020-08-19 — read the official letter on osha.gov →
Interpretation letters explain how OSHA applies its rules to specific situations. Always verify current requirements — regulations and enforcement policies change.

Get answers like this in seconds — with the receipts

Canary AI answers safety & compliance questions from the actual standards and interpretation letters, cites the exact section, and drafts JHAs as clean PDFs. Free during the pilot.

Join the pilot →

Related answers

Our testing facility uses automated turrets and a corrosive liquid, and the cake promised to employees never materialized. Where does OSHA stand?Machines & Electrical · OSHA letter 2019-06-19When two utilities share a pole, who is the host employer under OSHA Subpart V information transfer rules?Machines & Electrical · OSHA letter 2019-05-06Can lockout tags be placed at ground level instead of on elevated disconnecting means for transmission line work?Machines & Electrical · OSHA letter 2020-01-31